CTM5LR/CTM9LR Series Distributed Photovoltaic Grid-Connected Recloser Circuit Breaker

Home / Products / Automatic Recloser Circuit Breaker / CTM5LR/CTM9LR Series Distributed Photovoltaic Grid-Connected Recloser Circuit Breaker

  • CTM5LR/CTM9LR Series Distributed Photovoltaic Grid-Connected Recloser Circuit Breaker
  • CTM5LR/CTM9LR Series Distributed Photovoltaic Grid-Connected Recloser Circuit Breaker
  • Product Details
  • FAQ
Model CTM5LR-125GZS CTM9LR-250GZS
Frame grade rated current lnm(A) 125  250 
Pole 3P+N/4P 3P+N/4P
Rated current(adjustable)In(A) (0.4~1.0)ln (0.4~1.0)In
Rated insulation voltage Ui(V) 1000  1000 
Rated working voltage Ue(V) AC380/400/415 AC380/400/415
Rated impulse withstand voltage Uimp(KV) 12 
Rated limit short-circuit breaking capacity class M M H
Rated limit short-circuit breaking capacity lcu(kA) AC400V 25  50  85 
Rated running short-circuit breaking capacity Ics(kA) AC400V 17.5  35  50 
Rated short time withstand current Icw(kA)/1s 10 
Rated residual operated current I△n(mA) 30/50/75/100/200/300/500/OFF step regulation(non time delay type)
50/75/100/200/300/500/800/1000/OFF step regulation (time delay type)
Overvoltage operated value 280V±5%default as OFF, and it can be ON 310V±5%(photovoltaic)
Undervoltage operated value 165V±5%default as OFF, and it can be ON